Part # 461006
MODEL PVF
INDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITS
Installation, Operation and Maintenance Manual
®
RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING!!!
Improper installation, adjustment, alteration, service or maintenance can cause injury or death.
Read the installation, operating and maintenance instructions thoroughly before installing or
servicing this equipment.
CAUTION!!!
Units are designed for outdoor installation only. DO NOT locate units indoors.
Shipping
Check the unit for shipping damage. If any shipping damage is found, it should be reported to the last carrier
and your local Greenheck representative.
Indirect Fired Gas Unit Installations
Units are listed for installation in the United States and Canada
Installation of gas fired duct furnaces must conform with local building codes. In the absence of local
codes, installation must conform to the National Fuel Gas code, ANSI Z223.1 or in Canada,
CAN/CGA-B149 installation codes.
All electrical wiring must be in accordance with the regulation of the National Electric Code,
ANSI/NFPA No. 70.
•Unit is approved for installation downstream from refrigeration units. In these conditions, condensate
could form in the duct furnace and provision must be made to dispose of the condensate.
Refer to Part Number 460945 for any unit information other than that pertaining to the Indirect Fired Furnace.
R
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - MODEL PVF

Part # 461006MODEL PVFINDIRECT GAS FIRED FURNACES FOR ENERGY RECOVERY UNITSInstallation, Operation and Maintenance Manual®RETAIN THESE INSTRUCTIONS FO

Page 2 - Location Recommendations

1. Single furnaces (furnace input 100 to 400 MBH)have a single 3⁄4 inch connection. Double furnaces(furnace input 500 to 800 MBH) have two 3⁄4 inchcon

Page 3 - Electrical Connections

1. Installation of wiring must conform with local building codes. In the absence of local codes, installationmust conform to the National Electric Cod

Page 4 - Recovery from Lockout

Power-up/StandbyAfter power is supplied to the unit:1. The ignition control will reset and perform a self-check routine.2. The diagnostic LED will

Page 5 - Furnace Controls

Setting Manifold Pressure for Two Stage Gas Control1. Set the unit to high fire by setting thedischarge temperature control orthermostat to its maximu

Page 6

1. Set the unit to high fire by placing a jumper between terminals 7 and 8 on the Maxitrol amplifier.2. Measure the burner manifold pressure at each

Page 7 - Troubleshooting

Ignition Control Diagnostic LEDDuring normal operation, the LED is shut off. The LEDwill be on or flashing during a fault condition. If a faultconditi

Page 8 - Routine Maintenance

Combustion Blower MotorMotor maintenance is generally limited to cleaning.Cleaning should be limited to exterior surfaces only.Removing dust and greas